Product page

613 Series Cage-Protected Submersible Level Transmitters

The NOSHOK 613 Series Submersible Level Transmitter is specifically engineered for severe-service hydrostatic level measurement in viscous, slurry, sludge, and debris-laden applications such as municipal lift stations, sewage treatment wet wells, storm canals, and industrial wastewater basins. It features a heavy-duty 316 Stainless Steel cage assembly with a large 3.75" (95 mm) diameter active sensing area that protects the sensing diaphragm from rags, rocks, and settling solids while preventing fouling and plugging. Offering standard ±0.25% BFSL accuracy (optional ±0.125% BFSL) across measuring spans from 0-5 psi (11.55 ftH2O) up to 0-300 psi (693 ftH2O), the 613 Series delivers reliable 4-20 mA 2-wire or 0-5 Vdc, 0-10 Vdc, and 0.5-2.5 Vdc analog outputs. Equipped with submersible vented polyurethane (PUR) or chemical-grade FEP cable, internal Kevlar strain relief, RFI/EMI/ESD suppression, and options for integrated PT100 RTD temperature sensors, lightning surge protection (1.5 J), lifting rings, and NEMA 4X desiccant junction boxes.

Heavy-duty 316 Stainless Steel cage design protects diaphragm from settling sludge, rags, rocks, and slurry particulates

Large Ø 3.75" (95 mm) non-fouling sensing area prevents plugging in viscous and high-solids wastewater

High accuracy: ±0.25% full scale (BFSL) standard; optional high accuracy ±0.125% full scale (BFSL)

Pressure and level ranges from 0 psi to 5 psi (11.55 ftH2O) through 0 psi to 300 psi (693 ftH2O / 211 mH2O column depth)

Ready for quotationShare your range, connection and case requirement.
Talk to ATH

Technical data

Selection and ordering reference

Configure level range, accuracy (±0.25% or ±0.125%), output signal, cable length, and options for the NOSHOK 613 Series Cage-Protected Submersible Level Transmitter.

Cage base diameterØ 3.75" (95 mm) 316 SS
Pressure ranges0-5 psi to 0-300 psi (693 ftH2O)
Accuracy±0.25% BFSL (±0.125% opt)
Output signals4-20 mA, 0-5 V, 0-10 V, 0.5-2.5 V
WeightApprox. 3.2 lb (1.45 kg)
Submersion depthIP68 Submersible

Series

613Cage-Protected Submersible Level Transmitter (Ø 3.75" Cage Base)

Pressure & Level Ranges

5 psi0 psi to 5 psi (11.55 ftH2O / 3.52 mH2O)
10 psi0 psi to 10 psi (23.10 ftH2O / 7.04 mH2O)
15 psi0 psi to 15 psi (34.65 ftH2O / 10.56 mH2O)
20 psi0 psi to 20 psi (46.20 ftH2O / 14.08 mH2O)
30 psi0 psi to 30 psi (69.30 ftH2O / 21.12 mH2O)
50 psi0 psi to 50 psi (115.50 ftH2O / 35.20 mH2O)
75 psi0 psi to 75 psi (173.25 ftH2O / 52.80 mH2O)
100 psi0 psi to 100 psi (231.00 ftH2O / 70.41 mH2O)
150 psi0 psi to 150 psi (346.50 ftH2O / 105.61 mH2O)
300 psi0 psi to 300 psi (693.00 ftH2O / 211.23 mH2O)

Accuracy

1±0.25% full scale (BFSL) standard
2±0.125% full scale (BFSL) high accuracy

Output Signal

14 mA to 20 mA, 2-wire
20 Vdc to 5 Vdc, 3-wire
50 Vdc to 10 Vdc, 3-wire
110.5 Vdc to 2.5 Vdc, 3-wire

Electrical Connection & Cable

XXStandard Polyurethane (PUR) submersible cable (specify length in feet)
38-XXOptional FEP chemical-grade submersible cable (specify length in feet)

Options & Accessories

LR316 SS Lifting Ring top attachment
CBCCable clamp suspension bracket
PT1Integrated PT100 RTD 4-wire temperature sensor (*PUR only)
LPLightning surge protection (1.5 J per EN 61000-4-5, *PUR only)
DCDesiccant cartridge for vent tube moisture protection
FEFilter element for vent tube
JBNEMA 4X cable junction box with terminal strip

Part number example

613 - 5 - 1 - 1 - 50' - LR

613SeriesCage-protected level transmitter
5Range0 to 5 psi (11.55 ftH2O)
1Accuracy±0.25% BFSL
1Output4-20 mA 2-wire
50'Cable50 ft PUR cable
LROptionLifting Ring

Technical specifications

Cage diameterØ 3.75" (95 mm) 316 SS
Accuracy±0.25% BFSL (±0.125% opt)
Output options4-20 mA, 0-5 V, 0-10 V, 0.5-2.5 V
Wetted materials316 SS cage & body, PUR/FEP cable
WeightApprox. 3.2 lb (1.45 kg)
Submersion ratingIP68 Continuous

Operating notes

Large cage opening protects the flush diaphragm from sludge, slurries, and heavy particulates.

Integrated 3.2 lb ballast provides stable submersion during high fluid inflow and agitated pump cycles.

Vent tube must be protected with a desiccant cartridge (DC) or NEMA 4X junction box (JB) against ambient humidity.

Product Description

The NOSHOK 613 Series Cage-Protected Submersible Level Transmitter is purpose-built for harsh wastewater, slurry, and sludge monitoring where conventional submersible probes are vulnerable to clogging and physical damage. The rugged 316 stainless steel bird cage provides a wide standoff and large non-fouling opening, shielding the flush diaphragm from floating solids, fibrous rags, rocks, and thick sediments while maintaining unrestricted hydrostatic pressure transmission.

Each transmitter incorporates a precision piezoresistive sensing element with advanced temperature compensation, delivering exceptional measurement repeatability in outdoor storm canals and underground lift stations. The heavy 3.2 lb stainless steel structure provides natural ballast to keep the probe stably submerged during turbulent inflow conditions, and the integrated vent tube ensures continuous barometric equilibrium.

Heavy-gauge 316 SS cage assembly prevents mechanical impact and solids buildup across the sensing diaphragm

Broad range options from 5 psi (11.55 ftH2O) to 300 psi (693 ftH2O) cover shallow wet wells and deep retention basins

Universal analog output interfaces (4-20 mA, 0-5 V, 0-10 V, 0.5-2.5 V) connect directly to municipal RTUs and plant SCADA

Substantial 3.2 lb body weight prevents floating and maintains vertical orientation in turbulent lift stations

Optional lightning protection (1.5 J) safeguards remote stormwater canal monitoring stations during electrical storms

Ordering Information

Series613 (Cage-protected submersible level transmitter)
Pressure ranges (psi / ftH2O)5 (0-5 psi / 11.55 ftH2O), 10 (0-10 psi / 23.10 ftH2O), 15 (0-15 psi / 34.65 ftH2O), 20 (0-20 psi / 46.20 ftH2O), 30 (0-30 psi / 69.30 ftH2O), 50 (0-50 psi / 115.50 ftH2O), 75 (0-75 psi / 173.25 ftH2O), 100 (0-100 psi / 231.00 ftH2O), 150 (0-150 psi / 346.50 ftH2O), 300 (0-300 psi / 693.00 ftH2O)
Accuracies1 = ±0.25% full scale (BFSL); 2 = ±0.125% full scale (BFSL)
Output signals1 = 4 mA to 20 mA, 2-wire; 2 = 0 Vdc to 5 Vdc, 3-wire; 5 = 0 Vdc to 10 Vdc, 3-wire; 11 = 0.5 Vdc to 2.5 Vdc, 3-wire
Electrical connectionsXX = Standard Polyurethane (PUR) cable (specify length in feet); 38-XX = Optional FEP cable (specify length in feet)
Options & AccessoriesCBC = Cable Clamp; DC = Desiccant Cartridge; FE = Filter Element; JB = NEMA 4X Cable Junction Box; LP = Lightning Protection (1.5 J, PUR only); LR = Lifting Ring; PT1 = PT100 RTD 4-wire (PUR only)

Part Number Example

Standard example613 - 5 - 1 - 1 - 50' - LR
Series613 = Cage-protected submersible level transmitter
Pressure range5 = 0 psi to 5 psi (11.55 ftH2O column depth)
Accuracy1 = ±0.25% full scale (BFSL)
Output signal1 = 4 mA to 20 mA, 2-wire
Electrical connection50' = 50 feet of submersible polyurethane (PUR) cable
OptionLR = Lifting Ring

Product Specifications

Accuracy±0.25% full scale (BFSL) standard; optional ±0.125% (BFSL)
Overpressure safetyProof pressure: 2x range; Burst pressure: 4x range
Temperature limitsMedia: 14 °F to 122 °F (-10 °C to 50 °C); Compensated: 32 °F to 122 °F (0 °C to 50 °C); Storage: -22 °F to 175 °F (-30 °C to 80 °C)
Temperature effect±0.01%/ °F for zero and span
Housing & Cage316 Stainless Steel cage (Ø 3.75" / 95 mm base, 4.44" / 113 mm height); 316 SS upper body (Ø 1.06" / 27 mm)
Environmental ratingIP68 continuous deep liquid submersion
Electromagnetic ratingBuilt to suppress RFI, EMI, and ESD interference
Electrical protectionReverse polarity, short circuit, and optional lightning protection per EN 61000-4-5 (1.5 J)
Vibration & Shock15 g according to IEC 60068-2-6; Shock 100 g according to IEC 60068-2-27
WeightApproximately 3.2 lb (1.45 kg) - cable extra

Operating Notes

The large 316 SS protective cage prevents solids from touching the sensing diaphragm, making it ideal for direct suspension in raw sewage lift stations, storm canals, and slurry tanks.

Always terminate the vented cable in a dry NEMA 4X junction box (JB) equipped with a desiccant cartridge (DC) or filter element (FE) to keep the internal atmospheric reference tube free of moisture.

Use the optional Lifting Ring (LR) or cable clamp (CBC) for secure mechanical suspension without exerting strain on the electrical conductors.

Heavy 3.2 lb body weight resists fluid turbulence and avoids the need for secondary anchor weights.

Fast ≤ 1 ms response time allows rapid pump cycle automation in municipal stormwater and wastewater lift stations.

Optional 4-wire PT100 RTD sensor provides concurrent liquid temperature telemetry over the same submersible drop cable.

WhatsApp+1 (305) 934-5364